11kV to 33kV PT Oil Cooled

11kV to 33kV Potential Transformer/Voltage Transformer

(Dead or Live tank Design)

National Electricals is one of the leading manufacturers of 11kV to 33kV oil filled/immersed in dead tank or live tank design potential transformer/Voltage transformer for outdoor installation. Our product is being manufactured using industrial best practices/processes and are 100% tested before final dispatch as per NABL guidelines in our state of the art fully equipped lab under the supervision of experiences and well qualified engineers. Our product is fully type tested as per latest standards from government/NABL approved laboratories like ERDA/CPRI.


Call Back

Request Callback


Our product confirms to following standards and latest amendments. All products are confirming to following standards:-

  • Specification

    • IS 3156: 1992
    • IS 335: 1983
    • IS 2099:: 1986
    • IS 5561

  • Title

    • Specification for Voltage Transformer/Potential Transformer
    • Specification for Transformer Oil
    • Specification for bushing for AC voltage above 1kV
    • Specification for Terminal Connector

Features:

 

  • Outer chamber or tank: Made of Mild Steel having inner and outer coats of branded primer and enamel paint or hot dipped galvanised as per customer’s requirement.
  • Insulators: Procured from reputed manufacturers like GE, Tayal etc, confirm to latest IS standards and specifications having sufficient creep age distance.
  • Primary and Secondary Winding: Coated Super Enamelled round copper wire from reputed manufacturer like BIC, Atlas etc confirming to latest IS Standards is used. Insulation using high quality craft paper is done with alternate layers.
  • Core: High Quality core is used in PT.
  • Transformer Oil: The oil is filtered with 5 stage filtration process like heating degassing, vacuumed and dried etc and filled under vacuum. Transformer oil is confirming to IS 335 and procured from reputed suppliers like APAR, Savita.
  • Testing: Each unit undergoes all routine tests in our state of the art lab, by our well experienced and well qualified engineers before dispatch.
  • General Particulars

    • Highest System Voltage( H.S.V.)
    • Power frequency dry/ wet withstand voltage on the primary winding for one minute
    • Lightning Impulse withstand Voltage

  • 11KV

    • 12 KV (r.m.s.)
    • 28 KV (r.m.s.)

     

    • 75 KV (r.m.s.)

  • 33KV

    • 36 KV (r.m.s.)
    • 70 KV (r.m.s.)

     

    • 170 KV (r.m.s.)

  • Specific Particulars

    • Number pf Phases
    • Rated Transformation Voltage Ratio
    • Number of Secondary Windings
    • Output Burden
    • Accuracy Class
    • Voltage Factor

    • 3 or 1 unearthed or earthed & 1 earthed
    • As per customer requirement
    • Upto 3 or As per customer requirement
    • Upto 100VA( As per customer requirement)
    • For Metering: 2,0.2s 0.5,0.5s 1.0 & 3.0. For Protection: 3P,6P For 3 Phase RVT: 5PR, 10PR,15PR
    • 1.2 Continuous & 1.5 for 30 Sec or 1.9 for 30 Sec or 1.9 for 8 hours